Design Features:
Lightweight and compact, the AMCOT cooling tower provides quick and easy installation. Job site assembly is simplified by the modular design of all components. Prevailing wind directions will not affect cooling tower performance due to the unique circular design of the basin and casing.
Casing:
Easy access through casing simplifies cleaning. Individual fiberglass panels are stainless steel bolted together for periodic wash down and general clean up. The AMCOT FRP cooling tower is designed for durability and long life even under the most severe environmental weather conditions.
Fan Blades:
Aerodynamically designed propeller type fan blades are used to conserve power and assure quiet operation. AMCOT model ST-3 through ST-50 feature a factory balanced ABS plastic blade. AMCOT model ST-60 and above feature an all aluminum alloy adjustable fan.
Fan Motor:
AMCOT ST-3 through ST-200 has a direct drive motor. AMCOT ST-225 and larger feature a unique belt drive design to reduce noise levels to a minimum.
Water Distribution System:
AMCOT ST-3 through ST-60 uses an ABS plastic sprinkler with stainless steel shaft. AMCOT ST-70 and above use an aluminum alloy sprinkler head. Both types of sprinkler heads require little or no head pressure loss and minimum maintenance.
Inlet Louvers:
Non rusting PVC plastic mesh provides easy access to sump while preventing foreign objects from entering water basin.
Ladder:
Provided for maintenance and inspection accessibility to fan and sprinkler systems. (Models ST-40 and above)
Fill Material:
Honeycomb heat embossed PVC is formed to permit high heat transfer efficiency. The AMCOT fill is suitable for operation with inlet water temperature up to 115F. For temperature above this please select ST-P(polypropylene) or STW(wood) models.
CAPACITY RATED: 95F Inlet and 85F Outlet Water with 78F Wet Bulb. Tons of Refrigeration at 12,000 BTU/HR with 3 GPM/Ton.